Features:
- Alternating current transducer
- Choice of supply voltages
- Single phase AC
- Accuracy 0.5 (20....120%.In)
- Current input 1, 1.2, 5 or 6A
- Dip switch programmable current or voltage analogue output
- Available with 230Vac, 115Vac and 20-150Vdc auxiliary supply
Share Product:
விவரம்
To measure average value, calibration according RMS value Input on CT/1A - CT/5A Output selectable on field (7 ranges)
AUXILIARY SUPPLY
- Rated value Uaux ac: 48 - 115 – 230 and 240V
- Other value on request
- Tolerance: 0,9…1,1Uaux – 40…60V (Uaux 48V)
- Rated frequency faux: 50Hz
- Tolerance: 47…63Hz
- Rated burden: ≤ 3VA
- Rated value Uaux dc: 20…150Vdc – 150…250Vdc
- Rated burden: ≤ 1,5W
- Protected against incorrect polarity
OUTPUT
- Type: unidirectional, real or live zero for variable output load
- Accuracy (EN 60688): class 0,5
- Ripple content (EN 60688): ≤ 1%
- Response time (EN 60688): ≤ 300 ms
- Rated value: selectable by dip switch (7 ranges)
- Current rated values: 0…5 - 0…10 - 0…20mA - 4…20mA
- Compliance voltage: 15V
- Output load: 750W (20mA) - 1,5kW (10mA) - 3kW (5mA)
- Voltage rated values: 0…5 - 0…10 - 2…10V
- Output load: ≥ 5kW
HOUSING
- Dimensions: 2 module DIN 43880
- Connections: screw terminals for cable up to 4mm2
- Mounting: snap-on 35mm rail
- Rail type: top hat TH35-15 (EN60715)
- Housing material: self-extinguishing makrolon
- Protection degree (EN 60529): IP40 (front frame), IP20 (terminals)
- Weight: 200 grams